H05VV-F

H05VV-F
H05VV-F Low Voltage and Power Cables (PVC)
H05VVF F Önden
H05VV-F Low Voltage and Power Cables (PVC)
H05VVF F Üstten
H05VV-F Low Voltage and Power Cables (PVC)

H05VV-F

Type PVC Insulated, Mutli-core Cables with Flexible Conductor
Construction
 

Conductor: Fine-stranded copper (Class 5)

Insulation: Polyvinyl chloride (PVC)

Outer Sheath: Polyvinyl chloride (PVC)

Applications Used in dry and humid areas that there are not much mechanical compulsion in which, generally used in household equipments.
Standards TS EN 50525-2-11, BS EN 50525-2-11, DIN EN 50525-2-11, IEC 60227-5
high-conductor
flexible-structured

H05VV-F (300/500 V) / 318Y Cu/PVC/PVC
Nominal Cross Section (mm²) Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. (Ω/km) Current Carrying Capacity in Air(A)
2x0,75 5,9 55 26,0 6
2x1 6,3 64 19,5 10
2x1,5 7,2 87 13,3 16
2x2,5 8,9 133 7,98 25
2x4 10,9 184 4,95 32
3x0,75 6,3 65 26,0 6
3x1 6,7 75 19,5 10
3x1,5 7,8 106 13,3 16
3x2,5 9,6 163 7,98 25
3x4 11,0 226 4,95 32
4x0,75 6,8 77 26,0 6
4x1 7,4 93 19,5 10
4x1,5 8,7 131 13,3 16
4x2,5 10,5 197 7,98 25
4x4 12,0 275 4,95 32
5x0,75 7,8 97 26,0 6
5x1 8,3 113 19,5 10
5x1,5 9,9 164 13,3 16
5x2,5 12,8 248 7,98 25
5x4 13,6 347 4,95 32

​​​​​​

Min. bending radius

if D ≤ 12: 5 x D

if D > 12: 6 x D

Rated voltage Uo/U  300/500 V
Max. operating temperature  60 °C
AC test voltage  2 kV
Max. short-circuit temperature

 150 °C           

Flame propagation test on single cable  EN 60332-1
Lead-free  
EN 50575:2014+A1:2016 (H05VV-F,300/500 V,Eca)
Site İçi Arama
Make A Phone Call Send an E-mail
ONLINE CATALOG